Form 4 Type 2
Using the 3D graphic below please use the functions bar to further investigate the model. The functions include 3D orbit, zoom, section analysis and you can even explode the item to view all its individual parts
Tutorial & Explanation
The model demonstrates a Form 4 Type 2, Fully Compartmentalised unit. Therefore complying with all form 4 requirements, and adhering to Type 2 due the cable being glanded onto the gland plate in the adjacent cable chamber and directly connected to the breaker via the white partition ensuring compartmentalisation between breaker compartment and cable chamber

Image Demonstrating
Form 4 Type 2
from the BEAMA Guide
BEAMA Guide - Guide to Forms of Separation