top of page

Neutral Earthing Solution

Introduction

The only solution that we here come across is referred to and known as solidly neutral.

This being the common go-to solution for low voltage applications at 600 volts or less.

 

Explanation

In nearly all cases back at the star point of the transformer, the neutral is grounded and grounding conductor must be extended from the source to the furthest point of the system within the same raceway or conduit. The purpose of this is to maintain very low impedance to ground faults so that a relatively high fault current will flow thus ensuring that circuit breakers or fuses will clear the fault quickly and therefore minimise damage.

 

That is pretty simple, only other aspects to as keep at the back of your mind is you should only have a single neutral earthing link across an individual supply. Each individual supply should have a neutral earth. If in any case, a system is running two supplies in parallel and without a 4P breaker breaking 

the two supplies only one should be present.
Finally if you have, in particular, old UPS equipment or equipment that when the power is off and the mains incomer is 4P and the breaker is open and therefore the neutral earth link is broken. What impact will this have on your system? The reason I ask is old UPS systems or some UPS's won't have a connection to earth and this can cause problems as they have no reference to ground.

SIGN UP FOR OUR EMAIL UPDATES

Thanks, your one step closer to being ElecSpec Compliant

ElecSpec Logo.png
Designed around your specification, for all your Switchgear needs,
Igniting the Spark with ElecSpec

STAY CONNECTED WITH ELECSPEC

2020 ELECSPEC. ALL RIGHTS RESERVED

bottom of page